EOCR-SE2

support hotline

17717479099

SE2-05NS.png

EOCR-SE2 Overview

✔ Ultra-compact

✔ Overcurrent / Phase loss / Locked rotor protection 

    (Phase loss / Locked rotor detected by overcurrent action)

✔ Integrated startup delay / operation delay

✔ Manual (reset) / Motorized (remote) reset

✔ Ultra-energy-efficient

✔ No Voltage Release function (Fail-safe operation) → Type N

✔ Direct start type / Suitable for general small motor protection

✔ Easy wiring

EOCR-SE2 Applications

✔ CNC machine tool drill overload

✔ Compressor motor overload

✔ Crane overloading and low torque



Protection Features

✔ Overcurrent (Action after O-Time)

✔ Phase Loss (Action after O-Time)

✔ Locked Rotor (Action at O-Time)



EOCR-SE2Product Features

Main Information

Product NameEOCR-SE2

Product TypeEconomic Electronic Overcurrent Relay

Protection Type

Overload, In > Overcurrent Setting

Phase Loss

Locked Rotor, In > 3 times the Overcurrent Setting


[Us] Rated Input 

Voltage

S:24~240VAC/DC 

Protection Range

05:0.5~6A

30:3-30A

60:5-60


[Ui] Rated 

Insulation Voltage

600 V AC 50...60 Hz Main Circuit Conforming to UL

690 V AC 50...60 Hz Main Circuit Conforming to CSA

690 V AC 50...60 Hz Main Circuit Conforming to IEC 60947-4-1


Additional Information

Power Frequency50...60 Hz

Mounting Method35mm DIN rail mounting or screw fixing

Electromagnetic 

Compatibility

- Radiated RF immunity 10 V/m level 3 in accordance with IEC 61000-4-3

- Electrostatic discharge immunity 8 kV air, 6 kV contact in accordance with IEC 61000-4-2

- Transient overvoltage 2 kV in accordance with IEC 61000-4-4

- Conducted RF immunity 10 V in accordance with EN 61000-4-6

- Conducted RF emission class A in accordance with EN 55011


Contact Type & 

Composition

1 NO + 1 NC

[Ith]Continuous 

Current

5 A control circuit

[Uimp] Rated Impulse 

Withstand Voltage

6 kV Conforming to IEC 60947-4-1

Time SettingOvercurrent operating time (O-time) 1-15s

Power Consumption3W

Wiring

Control circuit: Terminal block 2 x 1…2.5 mm² without cable terminal - M3.5

Control circuit: Cable 2 x 1…2.5 mm² without cable terminal - M3.5

Control circuit: Cable 2 x 1…2.5 mm² with cable terminal - M3.5


Tightening Torque

Control circuit: 1.7 N·m, suitable for terminal clamps, cables, 7 mm

Main circuit: 1.7...2.5 N·m, suitable for terminal clamps, 7 mm


Using Environment

Standard
IEC 60947-4-1 

IP Rating
IP20 conforming to IEC 60529

Using Temperature
Matching IEC 60947-4-1, -20…60 °C

Storage Temperature
-30…80 °C

Using Altitude
2000m

Shock Resistance
15 gn 11 ms compliant with IEC 60068-2-7

Vibration Resistance

4 gn panel mounting in compliance with IEC 60068-2-6

2 gn 35mm DIN rail mounting in compliance with IEC 60068-2-6 


Surge Withstand
6 kV compliant with IEC 61000-4-5

Dielectric Strength

2 kV 50...60 Hz between enclosure and circuit in compliance with IEC 60255-5

1 kV 50...60 Hz between contacts in compliance with IEC 60255-5
2 kV 50...60 Hz between internal circuits in compliance with IEC 60255-5


Permissible Current
125 V, 5 A

Warranty 18 Months


EOCR-SE2  Reference Wiring

SE2-N型.png





SE2接线-N型.png

R型接点.png





SE2接线-R型.png


EOCR-SE2   Dimensions

SE2-05NS.png

SE2-外形尺寸.png



EOCR-SE2  Product Ordering

SE2选型.png


EOCR-SE2 Product List

Product ThumbnailCategoryModelCurrent RangeContact StatusControl Voltage
SE2-05NS.pngEOCRSE2-05NS0.5~6ANAC/DC 24~240V
30NS3~30A
60NS5~60A
05RS0.5~6AR
30RS3~30A
60RS5~60A


Online consultation