 | EOCR-SE2 Overview
✔ Ultra-compact ✔ Overcurrent / Phase loss / Locked rotor protection (Phase loss / Locked rotor detected by overcurrent action) ✔ Integrated startup delay / operation delay ✔ Manual (reset) / Motorized (remote) reset ✔ Ultra-energy-efficient ✔ No Voltage Release function (Fail-safe operation) → Type N ✔ Direct start type / Suitable for general small motor protection ✔ Easy wiring |
EOCR-SE2 Applications
✔ CNC machine tool drill overload
✔ Compressor motor overload
✔ Crane overloading and low torque
Protection Features
✔ Overcurrent (Action after O-Time)
✔ Phase Loss (Action after O-Time)
✔ Locked Rotor (Action at O-Time)
EOCR-SE2Product Features
| Product Type | Economic Electronic Overcurrent Relay |
| Protection Type | Overload, In > Overcurrent Setting
Phase Loss Locked Rotor, In > 3 times the Overcurrent Setting |
[Us] Rated Input Voltage | S:24~240VAC/DC |
| Protection Range | 05:0.5~6A 30:3-30A 60:5-60 |
[Ui] Rated Insulation Voltage | 600 V AC 50...60 Hz Main Circuit Conforming to UL
690 V AC 50...60 Hz Main Circuit Conforming to CSA 690 V AC 50...60 Hz Main Circuit Conforming to IEC 60947-4-1 |
| Power Frequency | 50...60 Hz |
| Mounting Method | 35mm DIN rail mounting or screw fixing |
Electromagnetic Compatibility | - Radiated RF immunity 10 V/m level 3 in accordance with IEC 61000-4-3
- Electrostatic discharge immunity 8 kV air, 6 kV contact in accordance with IEC 61000-4-2 - Transient overvoltage 2 kV in accordance with IEC 61000-4-4 - Conducted RF immunity 10 V in accordance with EN 61000-4-6 - Conducted RF emission class A in accordance with EN 55011 |
Contact Type & Composition | 1 NO + 1 NC |
[Ith]Continuous Current | 5 A control circuit |
[Uimp] Rated Impulse Withstand Voltage | 6 kV Conforming to IEC 60947-4-1 |
| Time Setting | Overcurrent operating time (O-time) 1-15s |
Wiring
| Control circuit: Terminal block 2 x 1…2.5 mm² without cable terminal - M3.5
Control circuit: Cable 2 x 1…2.5 mm² without cable terminal - M3.5 Control circuit: Cable 2 x 1…2.5 mm² with cable terminal - M3.5 |
Tightening Torque
| Control circuit: 1.7 N·m, suitable for terminal clamps, cables, 7 mm
Main circuit: 1.7...2.5 N·m, suitable for terminal clamps, 7 mm |
IP Rating
| IP20 conforming to IEC 60529 |
Using Temperature
| Matching IEC 60947-4-1, -20…60 °C |
Storage Temperature
| -30…80 °C |
Shock Resistance
| 15 gn 11 ms compliant with IEC 60068-2-7 |
| Vibration Resistance | 4 gn panel mounting in compliance with IEC 60068-2-6
2 gn 35mm DIN rail mounting in compliance with IEC 60068-2-6 |
Surge Withstand
| 6 kV compliant with IEC 61000-4-5 |
Dielectric Strength
| 2 kV 50...60 Hz between enclosure and circuit in compliance with IEC 60255-5
1 kV 50...60 Hz between contacts in compliance with IEC 60255-5 2 kV 50...60 Hz between internal circuits in compliance with IEC 60255-5 |
Permissible Current
| 125 V, 5 A |