PRODUCTS

your current location:Home - Products - EOCR motor protector

3E420

support hotline

17717479099

EOCR3E420-xxDUH.png

EOCR3E420-05AUT.png

EOCR-3E420 Overview

✔ Built-in MCU (Microcontroller Unit)

✔ Real-time processing / High precision

✔ Overcurrent protection range: 05: 0.5~7A, 80: 5-80A

✔ CT secondary side ratio setting: 1A/5A

✔ Output analog signal: 4~20mA

✔ Undercurrent protection range: Below overcurrent setting

✔ Operation time characteristics: Definite time / Inverse time

✔ Digital display screen

✔ Automatic three-phase current cyclic display: Digital ammeter

    (5-second interval for each phase) / Single-phase fixed management 

    function through manual cycling

✔ Trip cause digital display: Simple fault, self-diagnosis function

✔ Final trip cause confirmation: Records the last three trip causes and 

    allows confirmation of the current at the time of tripping

✔ Can be confirmed even after power outage recovery

✔ Manual (instant) / Automatic reset

✔ Fault protection function (FS: ON)

✔ Self-diagnosis function: Relay energization and normal operation 

     (selectable via setting)

✔ 35mm DIN rail mounting, suitable for various environments

✔ Suitable for variable frequency environments: 20~400Hz

✔ Selectable terminal type and through type

EOCR3E420-05DUH

EOCR3E420-80DUH

EOCR3E420-05DUT

EOCR3E420-80DUT


EOCR-3E420 Protection Functions

✔ Overcurrent (Definite time: 0.5...30 seconds, Inverse time: 1...30 levels)

✔ Undercurrent (0.5...30 seconds)

✔ Phase loss (within 3 seconds)

✔ Reverse phase (0.1...0.3 seconds)

✔ Current imbalance (within 8 seconds)

✔ Locked rotor (after D-Time)

EOCR-3E420 Product Features

Product Specifications

Product RangeEOCR

Model NameEOCR-3E420 Electronic Overcurrent Relay

Protection Type

• Overload protection, set value (In > Overcurrent setting value)

• Undercurrent protection, set value (In < Undercurrent setting value)

• Running locked rotor protection, set value (In > 1.5...5 times the overcurrent setting value)

• Phase loss protection

• Reverse phase protection

• Starting locked rotor protection, set value (In > 2...10 times the overcurrent setting value)

• Imbalance protection (5...50%)

• Current signal output: 4~20mA


 [Us] Rated 

Input Voltage

100~240V AC / AC


Power Frequency50...60 Hz

Relay applicationMotor protection

Protection Range• 05:0.5-7 A
• 80:5-80 A
• When used beyond the main body range with type 05 and 3CT, it can protect up to 960A

Mounting Method

35mm DIN rail mounting or screw fixing


Electrical/Mechanical Characteristics

Contact Type

• 1 NC + 1 NO (OL)

• 1 NO


[Ue]Rated 

Operational Voltage

600 V AC 50...60 Hz Main Circuit Conforming to UL

690 V AC 50...60 Hz Main Circuit Conforming to CSA

690 V AC 50...60 Hz Main Circuit Conforming to IEC 60947-4-1


[Uimp] Rated Impulse 

Withstand Voltage

6 kV Conforming to IEC 60947-4-1


Reset methodManual reset / Electric reset / Automatic reset

Time SettingOvercurrent operating time: 0.2...30 seconds (inverse time)

Display Type

Bar graph and 7-segment LED display


Power Consumption 5 W

[Ith] 

Continuous Current

3 A control circuit

Permissible Current100...240 V,3 A

Wiring

Control circuit cable: 2 x 1...1.5 mm² flexible cable with terminals - M3

Control circuit cable: 2 x 1...1.5 mm² flexible cable without terminals


Tightening Torque

Control circuit 0.8...1.2 N·m suitable for 4.7 mm cable


Dimensions and weight

type
Through bottm-hole type

Through screw-terminal type


Height56.3mm

56.3 mm


Width70mm

91.3 mm


Depth106

106


Weight280g640g

Using Environment

Using Temperature
Matching IEC 60947-4-1, -20…60 °C

Storage Temperature
-40…85 °C

Using Altitude
2000m

IP Rating
IP20 conforming to IEC 60529

Fire Resistance
650°C, compliant with IEC 60695-2-12 standard

Shock Resistance
15 gn 11 ms compliant with IEC 60068-2-7

Vibration Resistance

4 gn panel mounting in compliance with IEC 60068-2-6

2 gn 35mm DIN rail mounting in compliance with IEC 60068-2-6


Surge Withstand
6 kV compliant with IEC 61000-4-5

Dielectric Strength

2 kV 50...60 Hz between enclosure and circuit in compliance with IEC 60255-5

1 kV 50...60 Hz between contacts in compliance with IEC 60255-5

2 kV 50...60 Hz between internal circuits in compliance with IEC 60255-5


Electromagnetic 

Compatibility

- Radiated RF immunity 10 V/m level 3 in accordance with IEC 61000-4-3

- Electrostatic discharge immunity 8 kV air, 6 kV contact in accordance with IEC 61000-4-2

- Transient overvoltage 2 kV in accordance with IEC 61000-4-4

- Conducted RF immunity 10 V in accordance with EN 61000-4-6

- Conducted RF emission class A in accordance with EN 55011


Certification and standards

Standards
Matching IEC 60947-4-1

Certification
CE Certification

18 months warranty

EOCR-3E420 Reference Wiring

3DE-OFF - 副本.png

3DE-ON - 副本.png


EOCR-3E420 Dimensions

EOCR3DE-80DUH_IMAGE_1500x1500.png

外形图一体体式-2.png

EOCR3DE-05DUT.png

外形图一体体式-1.png


EOCR-3E420 Product Ordering

3E420-选型.png


Online consultation

If you are interested in our products, or if we can help you, you can call our national customer service number at any time:+86-17717479099