PRODUCTS

your current location:Home - Products - EOCR motor protector

3EZ

support hotline

17717479099
EOCR3EZ-xxCUH 拷贝.png

 EOCR-3EZ  Overview

✔ Built-in MCU (Microcontroller Unit)

✔ Real-time processing / High accuracy

✔ Integrated dedicated MCU microcontroller

✔ Current protection range: Model 05: 0.5~7A; Model 80: 5~80A

✔ For current above 80A, use external CT with Model 05 for protection, 

    secondary current can be set to 1A or 5A

✔ Digital display

✔ Power-off mode options: N and R

✔ 35mm DIN rail mounting

✔ Reset modes: Manual (RESET), power-off, and automatic reset options

✔ Suitable for 20~400Hz variable frequency environments

✔ Three fault records, data retained even during power outages

✔ Terminal or through-wiring options available

EOCR3EZ-05AUH      EOCR3EZ-80AUH

EOCR3EZ-05CUH      EOCR3EZ-80CUH

EOCR3EZ-xxAUT_1500x1500.png

EOCR3EZ-05AUT      EOCR3EZ-80AUT

EOCR3EZ-05CUT      EOCR3EZ-80CUT


EOCR-FEZ Protection Functions

✔ Overcurrent (Definite Time: 0.5...30 sec, Inverse Time: 1...30 levels)

✔ Undercurrent (0.5...30 sec)

✔ Phase Loss (within 3 sec)

✔ Reverse (0.1...0.3 sec)

✔ Current Imbalance (within 8 sec)

✔ Locked Rotor (after D-Time)

✔ Ground Fault (0.03...10 sec)


EOCR-3EZ  Product Features

Product Specifications

Product RangeEOCR

Model NameEOCR-3EZ Electronic Overcurrent Relay

Protection Type

• Overload Protection, Setting Value (In > Overcurrent Setting Value)

• Undercurrent Protection, Setting Value (In < Undercurrent Setting Value)

• Locked Rotor Protection During Operation, Setting Value (In > 1.5...5 times Overcurrent Setting Value)

• Phase Loss Protection

• Phase Reversal Protection

• Locked Rotor Protection During Start-up, Setting Value (In > 2...10 times Overcurrent Setting Value)

• Imbalance Protection (5...50%)

• Ground Fault Protection, Setting Value (Ig > Ground Fault Setting Value)


 [Us] Rated 

Input Voltage

100~240V AC / AC


Power Frequency50...60 Hz

 Relay applicationMotor protection

Protection Range

05:0.5-7 A
80:5-80 A

When Used with External CT:

Primary: 10-800 A

Secondary: 1 A, 5 A


Ground Fault 

Current (Ec)

0.03-10A


Mounting Method

35mm DIN rail mounting or screw fixing


Electrical/Mechanical Characteristics

Contact Type

Type A:

1 NC + 1 NO (OL): One normally closed contact and one normally open contact for overload protection

1 NO (GR): One normally open contact for ground fault protection

Type C:

1 NC + 1 NO (OL): One normally closed contact and one normally open contact for overload protection

1 NO (AL): One normally open contact for alarm function


[Ue]Rated 

Operational Voltage

600 V AC 50...60 Hz Main Circuit Conforming to UL

690 V AC 50...60 Hz Main Circuit Conforming to CSA

690 V AC 50...60 Hz Main Circuit Conforming to IEC 60947-4-1


[Uimp] Rated Impulse 

Withstand Voltage

6 kV Conforming to IEC 60947-4-1


Reset methodManual reset / Electric reset / Automatic reset

Time SettingOvercurrent Trip Time: 0.2...30 seconds (Inverse Time)

Display Type

Bar graph and 7-segment LED display


Power Consumption 5 W

Continuous Current3 A control circuit

Permissible Current100...240 V,3 A

Wiring

Control Circuit Cable: 2 x 1…1.5 mm² Flexible Cable with Terminals - M3

Control Circuit Cable: 2 x 1…1.5 mm² Flexible Cable without Terminals


Tightening Torque

Control circuit 0.8...1.2 N·m suitable for 4.7 mm cable


Dimensions and weight

type
Through bottm-hole type

Through screw-terminal type


Height56.3mm

91.3 mm


Width70mm

70 mm


Depth106

106


Weight470g640g

Using Environment

Using Temperature
Matching IEC 60947-4-1, -20…60 °C

Storage Temperature
-40…85 °C

Using Altitude
2000m

IP Rating
IP20 conforming to IEC 60529

Fire Resistance
650°C, compliant with IEC 60695-2-12 standard

Shock Resistance
15 gn 11 ms compliant with IEC 60068-2-7

Vibration Resistance

4 gn panel mounting in compliance with IEC 60068-2-6

2 gn 35mm DIN rail mounting in compliance with IEC 60068-2-6


Surge Withstand
6 kV compliant with IEC 61000-4-5

Dielectric Strength

2 kV 50...60 Hz between enclosure and circuit in compliance with IEC 60255-5

1 kV 50...60 Hz between contacts in compliance with IEC 60255-5

2 kV 50...60 Hz between internal circuits in compliance with IEC 60255-5


Electromagnetic 

Compatibility

- Radiated RF immunity 10 V/m level 3 in accordance with IEC 61000-4-3

- Electrostatic discharge immunity 8 kV air, 6 kV contact in accordance with IEC 61000-4-2

- Transient overvoltage 2 kV in accordance with IEC 61000-4-4

- Conducted RF immunity 10 V in accordance with EN 61000-4-6

- Conducted RF emission class A in accordance with EN 55011


Certification and standards

Standards
Matching IEC 60947-4-1

Certification
CE

18 months warranty

EOCR-3EZ Reference Wiring

3EZ-A型 - 副本.png

3EZ-C型.png

※ When FS is set to ON and operating power is applied to A1, A2, 

      OL output 97┤├98 switches to OFF

※ The ZCT terminal must be used without grounding

※ When FS is set to ON and operating power is applied to A1, A2, 

      OL output 97┤├98 switches to OFF

※ The ZCT terminal must be used without grounding

※ The control power should be supplied by an isolation transformer

      connected between phases

※ The control power should be supplied by an isolation transformer

      connected between phases


EOCR-3EZ Dimensions

EOCR3EZ-xxCUH 拷贝.png

分体外形图-H.png

EOCR3EZ-xxAUT_1500x1500.png

分体外形-T.png



EOCR-3EZ Product Ordering

3EZ-选型.png


Online consultation

If you are interested in our products, or if we can help you, you can call our national customer service number at any time:+86-17717479099

You can also communicate with us online, of course, you can also leave us a message below, we will be happy to serve you!