EOCR-3MZ2 Overview

✔ Built-in MCU (Microcontroller Unit) enhances measurement accuracy (1% level)

✔ High-frequency component filtering - Function to measure leakage current by 

     eliminating high-frequency components and pulse noise

✔ Harmonic Distortion Rate Measurement (THD) and Alarm Output

✔ Protection Functions: Overcurrent, Undercurrent, Phase Loss, Reverse Phase,  Ground 

     Fault, Imbalance, Locked Rotor during Start-up, Locked Rotor during Operation

✔ Auxiliary Functions: Runtime Storage, Fault Cause Storage, Restart Limit Function, 

    Fail-Safe Function

✔ Enhanced Monitoring Functions: 

    Three-phase current and leakage current, action causes

✔ Bar Graph Display Function

✔ Compatible with Three-phase and Single-phase

✔ Three-phase Current and Leakage Current Cycling Display Function

✔ For FMZ2, protection functions and actions will not be affected even if the 

    display window is removed

✔ Compliant with RoHS

3BZ2-WRAUTZ_IMG_1500x1500.png


EOCR-3MZ2 Protection Functions

✔ Overcurrent (Definite time: 0.2...30 seconds, Inverse time: 1...30 class)

✔ Undercurrent (Definite time: 0.5...30 seconds)

✔ Phase Loss (OFF, within 0.5...5 seconds)

✔ Reverse Phase (0.15 seconds)

✔ Current Imbalance (1...10 seconds)

✔ Locked Rotor During Start-up (0.5 seconds after D-Time)

✔ Locked Rotor During Operation (0.2...10 seconds)

✔ Ground Current (Settable: 0.03~10 seconds)


EOCR-3MZ2 Product Features

Product Information

Product RangeEOCR

Model NameEOCR-FMZ2 Motor Protection Relay

保护类型

Overload Protection, In > Overcurrent Setting

Underload Protection, In < Undercurrent Setting

Locked Rotor During Start-up, In > 2...8 times overcurrent setting

Locked Rotor During Operation, In > 1.5...5 times overcurrent setting

Phase Loss Protection

Imbalance Protection, 10...50%

Ground Fault Protection, Ig > Ground Current Setting

Reverse Phase Protection


[Us]

Rated Input Voltage

100...240 V AC/DC

Power Frequency50...60 Hz

Protection Range

0.5...32 A (Inverse time, thermal accumulation inverse time)

0.5...80 A (Definite time)

0.03...10 A (Definite time) - Ground Fault Current


Mounting Method

35 mm DIN Rail

Panel Mounting


Electrical/Mechanical Characteristics

Contact Type
 & Composition

A type : 1 NO, OL & 1 NO, GR

C type : 1 NC+1 NO, OL/GR

D type : 1 NC, OL & 1 NO, GR


Reset method

Manual reset

Automatic reset:0.5…1200 s

Electric reset:0…1 s


Time Setting

Start-up Delay Time: 0...200 seconds

Overcurrent Action Time: 0.2...30 seconds (Definite time)

Overcurrent Action Time: 1...30 class (Inverse time, thermal accumulation inverse time)

Undercurrent Action Time: 0.5...30 seconds

Ground Fault Action Time: 0.03...10 seconds

Ground Fault Action Delay Time During Start-up: 0...30 seconds


[Ue]Rated 

Operational Voltage

600 V AC 50...60 Hz Main Circuit Conforming to UL

690 V AC 50...60 Hz Main Circuit Conforming to CSA

690 V AC 50...60 Hz Main Circuit Conforming to IEC 60947-4-1


[Uimp]Rated Impulse

 Withstand Voltage

6 kV Conforming to IEC 60947-4-1

Power Consumption 3 W

Display TypeBar graph and 7-segment LED display

[Ith]Continuous Current3 A control circuit

Permissible Current100...240 V, 3A

Wiring

Control Circuit Cable: 2 x 1…1.5 mm², Flexible Cable with Terminal - M3

Control Circuit Cable: 2 x 1…1.5 mm², Flexible Cable without Terminal - M3

Control Circuit Cable: 1 x 1…2.5 mm², Flexible Cable with Terminal - M3

Control Circuit Cable: 1 x 1…2.5 mm², Flexible Cable without Terminal - M3


Tightening Torque

Control Circuit: 0.8...1.2 N·m, Suitable for Cable, Diameter 4.7 mm

Main Circuit: 2.5 N·m, Suitable for Terminal Clamp, Diameter 11 mm


Dimensions and weight

FMZ2

Window hole typeThrough bottm-hole typeThrough screw-terminal type

Height

74.5 mm56.3 mm98.3 mm

Width

70 mm70 mm70 mm

 Depth

83.8 mm108.1 mm108.1 mm

Weight

0.397 kg
0.437 kg0.555  kg

Using Environment

Using TemperatureMatching IEC 60947-4-1, -20…60 °C

Storage Temperature

-40…85°C

Operating Altitude2000m

 IP RatingIP20 conforming to IEC 60529

Fire Resistance650°C, compliant with IEC 60695-2-12 standard

Shock Resistance15 gn 11 ms compliant with IEC 60068-2-7

Vibration Resistance

4 gn panel mounting in compliance with IEC 60068-2-6

2 gn 35mm DIN rail mounting in compliance with IEC 60068-2-6


Surge Withstand6 kV compliant with IEC 61000-4-5

Dielectric Strength

2 kV 50...60 Hz between enclosure and circuit in compliance with IEC 60255-5

1 kV 50...60 Hz between contacts in compliance with IEC 60255-5

2 kV 50...60 Hz between internal circuits in compliance with IEC 60255-5


Electromagnetic 

Compatibility

- Radiated RF immunity 10 V/m level 3 in accordance with IEC 61000-4-3

- Electrostatic discharge immunity 8 kV air, 6 kV contact in accordance with IEC 61000-4-2

- Transient overvoltage 2 kV in accordance with IEC 61000-4-4

- Conducted RF immunity 10 V in accordance with EN 61000-4-6

- Conducted RF emission class A in accordance with EN 55011


Certification and standards

StandardsIEC 60947-4-1

CertificationUL

18 months warranty


EOCR-3MZ2 Reference Wiring

Wiring Diagram for 3-Phase Motor (Output Contact Type A, a-a Contact)

3-A.png

Wiring Diagram for 3-Phase Motor (Output Contact Type C, Common Contact)

3-C.png

Wiring Diagram for 3-Phase Motor (Output Contact Type D, b-a Contact)

3MZ2-D型3相接线.png

Wiring Diagram for 3-Phase Motor (MCCB Circuit Breaker Example)  

Wiring diagram for tripping MCCBN in the event of a ground fault.

※发生接地故障时 使MCCB跳闸的接线图.png


EOCR-3MZ2  Dimensions

3DM2-WRDUWZ_IMG_1500x1500.png

一体n-1.png

3DM2-WRDUHZ_IMG_1500x1500.png

一体n-2.png

3BZ2-WRAUTZ_IMG_1500x1500.png

一体n-3.png


EOCR-3MZ2  Product Ordering

3MZ2-型.png


EOCR-3MZ2 Product List

Product ThumbnailCategoryModelControl VoltageContact Status

3DM2-WRDUWZ_IMG_1500x1500.png

Window hole type

EOCR-3MZ2

EOCR3MZ2-WRAUWZ

EOCR3MZ2-WRAUW(Stop)

AC/DC 100~240VA stype

EOCR3MZ2-WRABWZ

EOCR3MZ2-WRABW()

AC/DC 24V

3DM2-WRDUHZ_IMG_1500x1500.png

Through bottm-hole type

EOCR3MZ2-WRAUHZ

EOCR3MZ2-WRAUH(Stop)

AC/DC 100~240V

EOCR3MZ2-WRABHZ

EOCR3MZ2-WRABH(Stop)

AC/DC 24V

3BZ2-WRAUTZ_IMG_1500x1500.png

Through screw-terminal type

EOCR3MZ2-WRAUTZ

EOCR3MZ2-WRAUT(Stop)

AC/DC 100~240V

EOCR3MZ2-WRABTZ

EOCR3MZ2-WRABT(Stop)

AC/DC 24V
Product ThumbnailCategoryModelControl VoltageContact Status

3DM2-WRDUWZ_IMG_1500x1500.png

Window hole type

EOCR-3MZ2

EOCR3MZ2-WRCUWZ

EOCR3MZ2-WRCUW(Stop)

AC/DC 100~240Vstype

EOCR3MZ2-WRCBWZ

EOCR3MZ2-WRCBW(Stop)

AC/DC 24V

3DM2-WRDUHZ_IMG_1500x1500.png

Through bottm-hole type

EOCR3MZ2-WRCUHZ

EOCR3MZ2-WRCUH(Stop)

AC/DC 100~240V

EOCR3MZ2-WRCBHZ

EOCR3MZ2-WRCBH(Stop)

AC/DC 24V

3BZ2-WRAUTZ_IMG_1500x1500.png

Through screw-terminal type

EOCR3MZ2-WRCUTZ

EOCR3MZ2-WRCUT(Stop)

AC/DC 100~240V

EOCR3MZ2-WRCBTZ

EOCR3MZ2-WRCBT(Stop)

AC/DC 24V


Product ThumbnailCategoryModelControl VoltageContact Status

3DM2-WRDUWZ_IMG_1500x1500.png

Window hole type

EOCR-3MZ2

EOCR3MZ2-WRDUWZ

EOCR3MZ2-WRDUW(Stop)

AC/DC 100~240Vstype

EOCR3MZ2-WRDBWZ

EOCR3MZ2-WRDBW(Stop)

AC/DC 24V

3DM2-WRDUHZ_IMG_1500x1500.png

Through bottm-hole type

EOCR3MZ2-WRDUHZ

EOCR3MZ2-WRDUH(Stop)

AC/DC 100~240V

EOCR3MZ2-WRDBHZ

EOCR3MZ2-WRDBH(Stop)

AC/DC 24V

3BZ2-WRAUTZ_IMG_1500x1500.png

Through screw-terminal type

EOCR3MZ2-WRDUTZ

EOCR3MZ2-WRDUT(Stop)

AC/DC 100~240V

EOCR3MZ2-WRDBTZ

EOCR3MZ2-WRDBT(Stop)

AC/DC 24V