PRODUCTS

your current location:Home - Products - EOCR motor protector

FDE

support hotline

17717479099

EOCRFDE-xxDUH_1500x1500.png

EOCR-FDE Overview

✔ Built-in MCU (microprocessor controller)

✔ Real-time processing/high accuracy

✔ Overcurrent protection range: 05: 0.5~: 7A 80: 5-80A

✔ Transformer secondary side ratio setting: 1A/5A

✔ Undercurrent protection range: set below overcurrent

✔ Operation time characteristics: Definite time/inverse time

✔ Undercurrent trip output

✔ Undercurrent output and OC output share output,

✔ AL output (07-08) automatically converted to undercurrent (UC) dedicated output contact

✔ Digital display

✔ Three-phase current automatic cycle display: digital ammeter 

    (5 seconds interval for each phase)/1-phase fixed management function according to manual cycle

✔ Trip cause digital display: simple fault, self-diagnosis function

✔ Final trip cause confirmation function: record the last 3 trip causes and trip current confirmation function

✔ Can also be confirmed when power off and re-transmission

✔ Manual (immediate)/auto reset

✔ Fault protection function (FS:ON)

✔ Self-diagnosis function: relay power is on, function during normal operation (selected by setting)

✔ 35mm rail installation, suitable for a variety of environments

✔ Suitable for variable frequency environment system: 20~400Hz

✔ Terminal type and through-type available

EOCRFDE-05DUH

EOCRFDE-80DUH

EOCRFDE-xxDUT_1500x1500.png

EOCRFDE-05DUT

EOCRFDE-80DUT


EOCR-FDE protection function

Overcurrent (definite time: 0.5...30 seconds, inverse time: 1...30 levels)

✔ Undercurrent (0.5...30 seconds)

✔ Phase loss (within 3 seconds)

✔ Reversal (0.1...0.3)

✔ Current unbalance (within 8 seconds)

✔ Stall (after D-Time)

EOCR-FDE Product Features

Product Specifications

Product RangeEOCR

Model NameEOCR-FDE Electronic Overcurrent Relay

Protection Type

• Overload protection, set value (In > overcurrent set value)

• Undercurrent protection, set value (In < undercurrent set value)

• Stall protection during operation, set value (In > 1.5...5 times the overcurrent set value)

• Phase loss protection

• Reverse phase protection

• Stall protection during start-up, set value (In > 2...10 times the overcurrent set value)

• Unbalance protection, (5...50%)


[Us] Rated Input Voltage

100~240V AC / AC


Power Frequency50...60 Hz

Relay applicationMotor protection

Protection Range 05:0.5-7 A
• 80:5-80 A
• If the range exceeds the main body, use 05 type and 3CT, the maximum protection is 960A

Mounting Method

35mm rail mounting or screw fixing


 Electrical/Mechanical Characteristics

Contact Type

• 1 NC + 1 NO OL):one normally closed contact and one normally open contact for overload protection

• 1 NO AL):one normally open contact for alarm function


[Ue]Rated 

Operational Voltage

600 V AC 50...60 Hz Main Circuit Conforming to UL

690 V AC 50...60 Hz Main Circuit Conforming to CSA

690 V AC 50...60 Hz Main Circuit Conforming to IEC 60947-4-1


[Uimp] Rated Impulse 

Withstand Voltage

6 kV Conforming to IEC 60947-4-1


Reset methodManual Reset/ Electric Reset /  Automatic Reset

ime SettingOvercurrent Operation Time 1...30 Class (Inverse Time)

Display Type

Bar Graph and 7-Segment LED Display


Power Consumption5 W

[Ith] 

Continuous Current

3 A Control Circuit

Permissible Curren100...240 V,3 A

Wiring

Control Circuit Cable: 2 x 1…1.5 mm² Flexible Cable with Ferrule - M3

Control Circuit Cable: 2 x 1…1.5 mm² Flexible Cable without Ferrule - M3


Tightening Torque

Control Circuit 0.8...1.2 N·m with Cable Diameter of 4.7 mm


Dimensions and weight

Height

56.3 mm


Width

70 mm


Depth

106 mm


Weight

贯穿型=0.39 kg,端子型=0.56kg


Using Environment

Using Temperature
Matching IEC 60947-4-1, -20…60 °C

Storage Temperature
-40…85 °C

Using Altitude
2000m

IP Rating
IP20 conforming to IEC 60529

Fire Resistance
650°C, compliant with IEC 60695-2-12 standard

Shock Resistance
15 gn 11 ms compliant with IEC 60068-2-7

Vibration Resistance

4 gn panel mounting in compliance with IEC 60068-2-6

2 gn 35mm DIN rail mounting in compliance with IEC 60068-2-6 


Surge Withstand
6 kV compliant with IEC 61000-4-5

Dielectric Strength

2 kV 50...60 Hz between enclosure and circuit in compliance with IEC 60255-5

1 kV 50...60 Hz between contacts in compliance with IEC 60255-5

2 kV 50...60 Hz between internal circuits in compliance with IEC 60255-5 


Electromagnetic 

Compatibility

- Radiated RF immunity 10 V/m level 3 in accordance with IEC 61000-4-3

- Electrostatic discharge immunity 8 kV air, 6 kV contact in accordance with IEC 61000-4-2

- Transient overvoltage 2 kV in accordance with IEC 61000-4-4

- Conducted RF immunity 10 V in accordance with EN 61000-4-6

- Conducted RF emission class A in accordance with EN 55011


Certification and standards

Standards
Conforming to IEC 60947-4-1

Certification
CE Certification

18 months warranty

EOCR-FDE  Reference Wiring

3DE-OFF - 副本.png

3DE-ON - 副本.png



EOCR-FDE  Dimensions

EOCRFDE-xxDUH_1500x1500.png

分体外形图-H.png

EOCRFDE-xxDUT_1500x1500.png

分体外形-T.png

Brochure_Digital E_2022 (1)_page3_image.png

    

  面板-1.png                           面板-2.png                      面板-3.png



EOCR-FDE  Product Ordering

FDE-选型.png


Online consultation

If you are interested in our products, or if we can help you, you can call our national customer service number at any time:+86-17717479099

You can also communicate with us online, of course, you can also leave us a message below, we will be happy to serve you!