PRODUCTS

your current location:Home - Products - EOCR motor protector

FE420

support hotline

17717479099

EOCRFDE-xxDUH_1500x1500.png

EOCR-FE420 Overview

✔ Built-in MCU (Microcontroller Unit)

✔ Real-time processing / High precision

✔ Overcurrent protection range: 05: 0.5~7A, 80: 5-80A

✔ CT secondary side ratio setting: 1A/5A

✔ Output analog signal: 4~20mA

✔ Undercurrent protection range: Below overcurrent setting

✔ Operation time characteristics: Definite time / Inverse time

✔ Digital display screen

✔ Automatic three-phase current cyclic display: Digital ammeter (5-second interval for each phase) /

 Single-phase fixed management function through manual cycling

✔ Trip cause digital display: Simple fault, self-diagnosis function

✔ Final trip cause confirmation: Records the last three trip causes and allows confirmation of the curre

nt at the time of tripping

✔ Can be confirmed even after power outage recovery

✔ Manual (instant) / Automatic reset

✔ Fault protection function (FS: ON)

✔ Self-diagnosis function: Relay energization and normal operation (selectable via setting)

✔ 35mm DIN rail mounting, suitable for various environments

✔ Suitable for variable frequency environments: 20~400Hz

✔ Selectable terminal type and through type

EOCRFE420-05DUH

EOCRFE420-80DUH

EOCRFDE-xxDUT_1500x1500.png

EOCRFE420-05DUT

EOCRFE420-80DUT


EOCR-FE420 Protection Functions

✔ Overcurrent (Definite time: 0.5...30 seconds, Inverse time: 1...30 levels)

✔ Undercurrent (0.5...30 seconds)

✔ Phase loss (within 3 seconds)

✔ Reverse phase (0.1...0.3 seconds)

✔ Current imbalance (within 8 seconds)

✔ Locked rotor (after D-Time)

EOCR-FE420 Product Features

Product Specifications

Product RangeEOCR

Product NameEOCR-FE420 Electronic Overcurrent Relay

Protection Type

Overload protection, set value (In > Overcurrent setting value)

• Undercurrent protection, set value (In < Undercurrent setting value)

• Running locked rotor protection, set value (In > 1.5...5 times the overcurrent setting value)

• Phase loss protection

• Reverse phase protection

• Starting locked rotor protection, set value (In > 2...10 times the overcurrent setting value)

• Imbalance protection (5...50%)

• Current signal output: 4~20mA


[Us] Rated 

Input Voltage

100~240V AC / AC


Power Frequency50...60 Hz

Relay applicationMotor protection

Protection Range05:0.5-7 A
80:5-80 A
 When used beyond the main body range with type 05 and 3CT, it can protect up to 960A

Mounting Method

35mm DIN rail mounting or screw fixing


Electrical/Mechanical Characteristics

Contact Type 

• 1 NC + 1 NO (OL): One normally closed contact and one normally open contact for overload protection

• 1 NO: One individual normally open contact


[Ue] Rated 

Operational Voltage

600 V AC 50...60 Hz Main Circuit Conforming to UL

690 V AC 50...60 Hz Main Circuit Conforming to CSA

690 V AC 50...60 Hz Main Circuit Conforming to IEC 60947-4-1


[UImp] Rated Impulse

Withstand Voltage

6 kV Conforming to IEC 60947-4-1


Reset methodManual reset / Electric reset / Automatic reset

Time SettingOvercurrent operating time: 0.2...30 seconds (inverse time)

Display Type

Bar graph and 7-segment LED display


Power Consumption 5 W

[Ith] 

Continuous Current

3 A control circuit

Permissible Current100...240 V,3 A

 Wiring

Control circuit cable: 2 x 1...1.5 mm² flexible cable with terminals - M3

Control circuit cable: 2 x 1...1.5 mm² flexible cable without terminals


Tightening Torque

Control circuit 0.8...1.2 N·m suitable for 4.7 mm cabl


Dimensions and weight

type
Through bottm-hole type

Through screw-terminal type


Height56.3mm

56.3 mm


Width70mm

91.3 mm


Depth106

106


Weight470g640g

Split cable(Cable-3M )
125g

Using Environment

Using Temperature
Matching IEC 60947-4-1, -20…60 °C

Storage Temperature
-40…85 °C

Using Altitude
2000m

IP Rating
IIP20 conforming to IEC 60529

Fire Resistance
650°C, compliant with IEC 60695-2-12 standard

Shock Resistance
15 gn 11 ms compliant with IEC 60068-2-7

Vibration Resistance

4 gn panel mounting in compliance with IEC 60068-2-6

2 gn 35mm DIN rail mounting in compliance with IEC 60068-2-6


Surge Withstand
6 kV compliant with IEC 61000-4-5

Dielectric Strength

2 kV 50...60 Hz between enclosure and circuit in compliance with IEC 60255-5

1 kV 50...60 Hz between contacts in compliance with IEC 60255-5

2 kV 50...60 Hz between internal circuits in compliance with IEC 60255-5


Electromagnetic 

Compatibility

- Radiated RF immunity 10 V/m level 3 in accordance with IEC 61000-4-3

- Electrostatic discharge immunity 8 kV air, 6 kV contact in accordance with IEC 61000-4-2

- Transient overvoltage 2 kV in accordance with IEC 61000-4-4

- Conducted RF immunity 10 V in accordance with EN 61000-4-6

- Conducted RF emission class A in accordance with EN 55011


Certification and standards

Standards
Matching IEC 60947-4-1,

Certification
CE 

18 months warranty

EOCR-FE420 Reference Wiring

3E420-OFF无外框.png

3E420-ON无外框.png

The analog current (4-20mA) signal output is powered by a 4-wire system, 

so the input side must be connected to a 2-wire system

※ The control power should be supplied by an isolation transformer connected between phases

The analog current (4-20mA) signal output is powered by a 4-wire system, 

so the input side must be connected to a 2-wire system

※ The control power should be supplied by an isolation transformer connected between phases

EOCR-FE420 Dimensions

EOCRFDE-xxDUH_1500x1500.png

分体外形图-H.png

EOCRFDE-xxDUT_1500x1500.png

分体外形-T.png

Brochure_Digital E_2022 (1)_page3_image.png

    

  面板-1.png                           面板-2.png                      面板-3.png



EOCR-FE420  Product Ordering

FE420-选型.png


Online consultation

If you are interested in our products, or if we can help you, you can call our national customer service number at any time:+86-17717479099

You can also communicate with us online, of course, you can also leave us a message below, we will be happy to serve you!